MI3100 @MI3100%低壓電氣綜合測試儀MI-3100
·快速可靠準確回路電阻測量,不必RCD脫扣。MI3100 @MI3100% low voltage electrical tester MI-3100
Fast and reliable and accurate loop resistance measurement, not RCD trip.
Built in fuse characteristic database on line loopimpedance test, evaluation of test results.
· the actual verification of the ground test method, reduce the stray current testing.
· online voltage monitor test showed that L-L, L-N, L-PE level.
TN/TT/IT grounding system.
Multi function terminal connection, rapid sequencemeasurement.
Standard configuration with rechargeable batteries andcharger kit.
Standard application function: EN61577
Other test standards: IEC/EN6036461008;EN6100960755; AS/NZ3760; CEI64.8; BS7671, HD384,VDE413
Electromagnetic compatibility (EMC):EN61326;LVD:EN61010-1; EN61010-031
Insulation resistance (EN61557-2) line impedance(EN61557-3)
Measuring range: M Ω 0 ÷ 199.9 accuracy. ± (5%readings +3), Un:100V, 250V measurement range:0.00+19.99 Ω, 20+99.9100+1999; (5% ± reading +5)
0 / 199.9 accuracy. ± (2% readings +3), Un:500V,1000VIpsc0.00A, 24.4kA
200 / 199.9 accuracy. ± (10% readings), Un:500V, 1000Vrated voltage: 100V / 440V /45Hz / 65Hz
Rated voltage: 100V, 250V, 500V, 1kV fault loopimpedance RL-PE (EN61557-3)
Measure current: the minimum 1mA in RN=UNX1k Ω /V Ω 0.00+19.99 measurement range, 20+99.9100+1999; (5%± reading +5
Short circuit current: <3mAIPFC:0.00A / 24.4kA
Continuous rated voltage of 100V / 264V /45Hz / 65Hz
Low resistance: (EN61557-4) voltage and frequency
Measuring range: Omega 0 ÷ 19.9 accuracy. ± (3% readings +3) V:0+400V measurement range, precision. ±(2% readings +2)
20 / 99.9100+1999, the accuracy of ± (5% readings)
The test current: minimum ± 200mA, reproducing surveillance in 2. All measurements
The open circuit voltage: 6.5V / 9.0V measurement range of f:45Hz / 65Hz; (1% ± reading accuracy. +1)
Continuous 7mA phase rotation (EN61557-7)
Measuring range: 0 Ω / 99.9100+1999, (5% ± readingaccuracy. +3) shows the results of 1.2.3 or 2.1.3
The maximum test current: rated voltage of 8.5mA 100V /440V /45Hz / 65Hz
The open circuit voltage: 6.5V / 9.0V
RCD (EN61557-6) general
The measurement range of [I Δ N]10, 301003005001000mA power supply voltage 9VDC (6 x 1.5V batteries AA
Rated voltage of 100V / 264V/45Hz / 65Hz chargervoltage 12V / 15V
The contact voltage Uc overvoltage category 600V, class III
The measurement range of [V]0.0 / 9.9 accuracy.(0%/+10% reading +2) plug connection overvoltage
10 / 99.9 accuracy. (0%/+10% readings) species (300Voption), class III
RS0.00 Ω, 10.00k Ω, (RS=UC/I Δ N) protection for double insulat
The fault loop resistance pollution degree 2
RL0.00 Ω 1999k Ω, protection class IP
Tripping time lag free RCD display 128 x 64 dot matrixwith background light
X1:0ms / 300ms (500ms) 230 X115 thick size width X103 height
X2:0ms / 150ms (200ms) 1.32kg weight with battery
X5:0ms / 40ms (150ms), UC:0.0V / 100.0V operating temperature range 040oC
Tripping current I Δ: 0.2 × I Δ N = 1.1 × I Δ N (AC / 1.5 x I Δ N
T Δ: 0ms / 300ms, UC:0.0V / 100.0
Multiple X0.5, X1, X2, X5
Ordering information the MI 3100
Eurotest ESAI testing instrument
- line connection, with 2 function keys
Schuko plug test line
"Electrical apparatus measuring" manual, CD version
Power adapter +NiMN6AA battery
Test pen (black, blue, green)
Three - the crocodile clip
Soft pack straps
Soft pack
- concise user manual
CD version of a detailed user manual
- Certificate
Product technical data
The choice of accessories
The A1168 plug connection
A1169 fast 12 bit AA charger
A1110 cable
A1111 three-phase adapter
A1160 fast 6 bit AA charger
A1154 test wire, black 4 meters
A1153 test wire, black 20 meters
A1171 USB/RS232 adaptor with 1m fixed electrical