CA6472數字式多功能接地電阻測試儀@CA6472%
進行接地耦合測量與顯示,用于評估互不相連(獨立)的兩個接地電阻系統之間的影響
技術參數:
|
|
3極法
|
4極法/選擇性測量
|
雙鉗法
|
土壤電阻率
|
接地電位測量
|
直流電阻
測量
|
配合CA6474
測量
|
|
量程
|
0.01Ω-
99.9kΩ
|
0.001Ω-
99.9Ω
|
0.01Ω-
500Ω
|
0.01kΩ-
99.9kΩ
|
0.01mV-
65.00V
|
0.001Ω-
99.9kΩ
|
0.001Ω-
99.99kΩ
|
|
分辨率
|
0.01-
100Ω
|
0.001-
10Ω
|
0.01-
1Ω
|
0.01-
100Ω
|
0.01mV-
10mV
|
2線法:0.01Ω-100Ω
4線法:
0.001Ω-10Ω
|
0.001-10Ω
|
|
精度
|
±(2%+1
計數)
|
±(2%+1
計數)
|
±(10%+1計數)
|
±(2%+1
計數)
|
±(5%+1 計數)
|
±(2%+2 計數)
|
±(5%+1
計數)
|
|
空載電壓
|
16或32VRMS
|
±16VDC
|
16或32VRMS
|
||||
|
測試頻率
|
41-
5078Hz
|
41-
5078Hz
|
自動:1367Hz
手動:1367Hz/ 1611Hz/ 1758Hz
|
41-
128Hz
|
41-
128Hz
|
DC
|
41-5078Hz
|
|
耦合測量
|
有
|
-
|
-
|
-
|
-
|
-
|
-
|
|
輔助地樁電阻測試
|
0.1Ω-
100kΩ
|
0.01Ω-
100kΩ
|
-
|
-
|
-
|
-
|
0.01Ω-
100kΩ
|
|
干擾電壓
|
最大60V峰值
|
|
最大60V
峰值
|
||||
|
測量方法
|
-
|
-
|
-
|
Wenner&
Schlum
berger法
自動計算
|
-
|
-
|
-
|
|
測量類型
|
3線
|
4線
|
-
|
4線
|
3線
|
2線或4線
|
-
|
|
電流測量
|
-
|
-
|
-
|
-
|
-
|
>200mA DC
|
-
|
|
內存容量
|
可存儲512組測量結果
|
||||||
|
通訊接口
|
光口通訊線/USB
|
||||||
|
防護等級
|
IP53
|
||||||
|
電氣安規
|
CAT IV 50V, 符合IEC 61326-1 / IEC 61010 / IEC61557-1-4-5
|
||||||
|
尺寸
|
260 x 240 x 120 mm
|
||||||
|
重量
|
3.2 kg
|
||||||
CA6472 digital multifunctional ground resistance tester@CA6472%
Digital multifunctional ground resistance tester CA6472,can be used to measure: ground loop connection pointresistance, grounding resistance (traditional pile methodor a clamp method), soil resistivity, ground coupling, andthe step voltage, contact potential etc..
As with the use of CA6474, can be used for themeasurement of grounding resistance of transmissiontower or wireless communication tower bar.
CA6472 grounding resistance measurement range, 0.01 to 99.99k Ω, automatic range function, can automatically switch to the best measurement range, and selects the best frequency measurement and current measurement. Measuring frequency can be set from 40 to 5078Hz configuration (manually or automatically); due to the adoption of high anti-interference design, can be used for a variety of complex and bad environment (such as the existence of discrete current measurement accuracy)
CA6472 can store 512 sets of measured data, candirectly view on the instrument, or by the DataView ®software to import the data into PC, automatically generate reports, potential distribution map, the test frequency / resistance graph etc..
Product features:
Available 4 pole (4 points) fall of potential method of measuring very low grounding resistance, and can bemanual or automatic selection of measuring frequency,and automatic test lead compensation
The use of 3 electrode potential drop method of grounding resistance measurement
The use of 3 coupling measurement method
High electrical noise environment, can test the frequencyselected manually or automatic frequency scanning 40Hzto 513Hz, ensuring measurement accuracy
Can choose the test voltage of 16V or 32V, measuring the current up to 250mA
Can use 4 electrode measurement of soil resistivity, and automatic calculation shows that Rho (P) one value; the user can choose Wenner method or Schlumberger method
Can be carried out in 2 line or 4 line method of measuring DC resistance (ground loop connection point resistance),with automatic current reverse function
Grounding resistance measurement by double clamp method (no need to call the auxiliary pile)
With CA 6474 and tower grounding test current clampspecial (GroundFlex ®), capable of measuring high voltage transmission and distribution on the rod foot of the leakage current and the grounding resistance, and does not need to disconnect the overhead ground wire
The standard DataView ® software, can be used to measure the data into the PC memory, real-time display,analysis, report generation and instrument configurationsettings
Automatic shutdown of power management features
Automatic recognition of the auxiliary electrode and the electrode resistance all connections
The instrument can test data memory stores a 512 set ofcomplete
Use only isolated USB communication interface
Use rechargeable nickel metal hydride (NiMH) battery as the power supply, purchase a car filled with optionalaccessories
Rugged dustproof rainproof casing design
Product application:
Using the 3 electrode method measuring grounding andgrounding resistance, typically used to disconnect the ground connection conductor occasions
Using the 4 electrode method for measurement of soil resistivity, soil resistivity minimum position, make thegrounding engineering is more reasonable, economy
The contact and step potential measurement. Unable todisconnect the ground wire of the situation, and thegrounding fault is likely to occur, or electrical device ofthe contact area with the ground, and the measuredground size is comparable, suggest potential measurement.
The use of 2 or 4 wire method to measure theconductivity of ground loop connection point (continuous),the test current is DC 250mA or higher, can be used for the detection of resistance grounding system allconnection points.
Ground coupling measurement and display, for the assessment of each other (independent) effect between the two grounding resistance system
Technical parameters:
3 pole 4 pole / double clamp method selective measurement of soil resistivity grounding of DC resistance measurement
Measurement with CA6474
Measurement
Range 0.01 Ω
99.9k Ω to 0.001 Ω
99.9 Omega 0.01 Omega
500 Ω 0.01K Ω
99.9k Ω 0.01mV
0.001 - 65.00V
99.9k Ω to 0.001 Ω
99.99k
Resolution 0.01-
100 - 0.001-
10 - 0.01-
1 - 0.01-
100 - 0.01mV-
10mV 2 line method: 0.01 Ω -100
4 line method:
0.001 Ω -10 Ω 0.001-10
Accuracy of ± (2%+1
Count (2%+1)
Count) ± (10%+1 count (2%+1)
Count) ± (5%+1 counts) ± (2%+2 count (5%+1)
Count)
The no-load voltage of 16 or 32VRMS ± 16VDC 16 or32VRMS
The frequency of test 41-
5078Hz 41-
5078Hz automatically: 1367Hz
Manual: 1367Hz/ 1611Hz/ 1758Hz 41-
128Hz 41-
128Hz DC 41-5078Hz
A - coupling measurement
Auxiliary pile resistance test 0.1 Ω
100k Ω to 0.01 Ω
100k Ω - Omega - 0.0
100K
The maximum 60V peak value of 60V interference voltage
Peak value
Measuring methods -- Wenner&
Schlum
The Berger method
Automatic calculation
Measurement of type 3 line 4 line 4 line 3 line 2 line or 4line
Current measurement, >200mA DC
Memory can store 512 groups of measurement results
Communication interface port communication line /USB
Protection class IP53
Electrical safety CAT IV 50V, with IEC 61326-1 / IEC 61010 / IEC61557-1-4-5
Size 260 x 240 x 120 mm
The weight of 3.2 kg